  "schemaVersion": 1,
  "kind": "workbook",
  "key": "mit-buildvac-ventilation/v1.0",
  "title": "MIT BuildVac Ventilation Requirements",
  "summary": "MIT BuildVac Ventilation Requirements with version-pinned publisher workbook calculations, scenario inputs and formula-level audit traces.",
  "edition": "v1.0",
  "html": "https://formualizer.com/catalog/mit-buildvac-ventilation",
  "parent": {
    "text": "https://formualizer.com/catalog/subjects/engineering/llms.txt",
    "json": "https://formualizer.com/catalog/subjects/engineering/llms.json"
  },
  "publisher": "MIT Sustainable Design Lab",
  "publisherPageUrl": "https://netzerobuildings.mit.edu/ventilation-requirements",
  "verificationLevel": "scenario-independent-arithmetic",
  "verificationExplanation": "Changed-input scenarios match an independent calculation.",
  "rightsExplanation": "This is an academic source; this catalog class does not establish a redistribution licence.",
  "limitations": [
    "Edition v1.0 is a catalog pin, not a separately established publisher release number.",
    "Heating uses the same cold supply temperature as cooling exactly as authored; this conceptual comparison is not full HVAC design.",
    "Runtime approximate VLOOKUP fails exact source default on unsorted Lists!A1:D18. Exact-match adaptation is bounded to documented program enum; source bytes are unchanged."
  ],
  "releaseBlockers": [],
  "licenseClass": "open-academic",
  "disclaimer": "Catalog calculations, not certification.",
  "removal": "Entries are removed on the publisher’s request.",
  "flows": [
    {
      "id": "quick_ventilation_shafts",
      "title": "Quick ventilation and shaft comparison",
      "description": "Compare DOAS and all-air shafts with coupled density/rate method switches. Supply all custom numeric ports when activating their methods. Baseline supply temperature 12.8°C and air properties remain pinned.",
      "inputPorts": [
        "program_area_m2",
        "program",
        "occupant_density_method",
        "custom_occupant_density",
        "flow_rate_method",
        "custom_flow_per_area",
        "custom_flow_per_person",
        "doas_velocity_m_per_s",
        "doas_safety_fraction",
        "peak_heating_kw",
        "peak_cooling_kw",
        "cooling_setpoint_c",
        "heating_setpoint_c",
        "all_air_velocity_m_per_s",
        "all_air_safety_fraction"
      ],
      "outputPorts": [
        "people_count",
        "outdoor_flow_l_per_s",
        "doas_total_shaft_m2",
        "all_air_total_shaft_m2",
        "shaft_comparison"
      ]
    },
    {
      "id": "full_ventilation_assessment",
      "title": "Full ventilation and all-air assessment",
      "description": "All source decision inputs including air properties and supply temperature, plus supply/return/exhaust diagnostics. Fixed return ratio 80%; source lookup table is pinned.",
      "inputPorts": [
        "program_area_m2",
        "program",
        "occupant_density_method",
        "custom_occupant_density",
        "flow_rate_method",
        "custom_flow_per_area",
        "custom_flow_per_person",
        "doas_velocity_m_per_s",
        "doas_safety_fraction",
        "peak_heating_kw",
        "peak_cooling_kw",
        "cooling_setpoint_c",
        "heating_setpoint_c",
        "supply_air_temperature_c",
        "air_specific_heat",
        "air_density",
        "all_air_velocity_m_per_s",
        "all_air_safety_fraction"
      ],
      "outputPorts": [
        "people_count",
        "outdoor_flow_l_per_s",
        "outdoor_flow_m3_per_s",
        "doas_supply_shaft_m2",
        "doas_exhaust_shaft_m2",
        "doas_total_shaft_m2",
        "heating_flow_m3_per_s",
        "cooling_flow_m3_per_s",
        "all_air_supply_shaft_m2",
        "all_air_return_shaft_m2",
        "all_air_total_shaft_m2",
        "shaft_comparison"
      ]
    }
  ],
  "example": {
    "id": "quick_ventilation_shafts_larger_office",
    "flow": "quick_ventilation_shafts",
    "inputs": {
      "program_area_m2": 10000
    },
    "expectedOutputs": {
      "people_count": 500,
      "outdoor_flow_l_per_s": 4250,
      "doas_total_shaft_m2": 1.2218749999999998,
      "all_air_total_shaft_m2": 6.995576139985888,
      "shaft_comparison": "Shafts for the all-air system are larger than shafts for the dedicated outdoor air system"
    },
    "inputsJson": "{\"program_area_m2\":10000}",
    "expectedOutputsJson": "{\"people_count\":500,\"outdoor_flow_l_per_s\":4250,\"doas_total_shaft_m2\":1.2218749999999998,\"all_air_total_shaft_m2\":6.995576139985888,\"shaft_comparison\":\"Shafts for the all-air system are larger than shafts for the dedicated outdoor air system\"}"
  },
  "ports": {
    "text": "https://formualizer.com/catalog/agents/mit-buildvac-ventilation/v1.0/ports/llms.txt",
    "json": "https://formualizer.com/catalog/agents/mit-buildvac-ventilation/v1.0/ports/llms.json"
  },
  "service": {
    "openapi": "https://catalog.formualizer.com/v1/models/mit-buildvac-ventilation/v1.0/openapi.json",
    "types": "https://catalog.formualizer.com/v1/models/mit-buildvac-ventilation/v1.0/types.d.ts",
    "fio": "https://catalog.formualizer.com/v1/models/mit-buildvac-ventilation/v1.0/fio.yaml",
    "evaluate": "https://catalog.formualizer.com/v1/models/mit-buildvac-ventilation/v1.0/evaluate",
    "mcp": "https://catalog.formualizer.com/v1/mcp"
  }
}