MIT BuildVac Ventilation Requirements
MIT Sustainable Design Lab
Estimate outdoor, heating and cooling airflow. Size supply and exhaust shafts for dedicated outdoor air and supply and return shafts for all-air systems.
- Inputs
- 18
- Outputs
- 12
- File size
- 35 KB
- Verification
- Independent scenario check
Try it
Try it loads a copy of this file from formualizer.com.
Saved workbook valuesInputOutput
| Row | B | C | D |
|---|---|---|---|
| 5 | Program Area (m2) | 5000 | |
| 6 | Program | Commercial - Office Buliding - Office Space | |
| 7 | Occupant Density Method | ASHRAE 62.1-2022 Occupant Density | |
| 9 | Total People Count | 250 | |
| 12 | Flow Rate Method | ASHRAE 62.1-2022 Flow Rates | |
| 19 | Air Velocity (m/s) | 8 | |
| 29 | Peak Heating Load (kW) | 170 | |
| 30 | Peak Cooling Load (kW) | 240 |
What was checked
Changed-input scenarios match an independent calculation.
Scope and limitations
Catalog calculations, not certification.
Try it uses Formualizer’s exact-match program lookups for the listed building types.
MIT BuildVac Ventilation Requirements with version-pinned publisher workbook calculations, scenario inputs and formula-level audit traces.
- Edition v1.0 is a catalog pin, not a separately established publisher release number.
- Heating uses the same cold supply temperature as cooling exactly as authored; this conceptual comparison is not full HVAC design.
- Runtime approximate VLOOKUP fails exact source default on unsorted Lists!A1:D18. Exact-match adaptation is bounded to documented program enum; source bytes are unchanged.
What it computes
Ports for the compact flow: quick_ventilation_shafts. The full port contract includes all 30 ports.
Inputs (15)
| Port / description | Type / constraints / default |
|---|---|
program_area_m2Nonnegative floor program area. Units: m². Omitted input retains publisher's source default 5000. | Type: number Constraints: min: 0 Default: 5000 |
programExact source program label; preserve source spelling Buliding and double spaces. Three lookups use documented exact-match preparation for these labels. Units: source enum. Omitted input retains publisher's source default "Commercial - Office Buliding - Office Space". | Type: string Constraints: one of: Commercial - Office Buliding - Lobbies and Corridors, Commercial - Office Buliding - Office Space, Education - Assembly, Education - Classrooms (5-8), Education - Classrooms (9+), Education - Lecture Classroom, Education - Lecture Hall, Education - Libraries, Education - University Laboratory, Public Assembly - Auditorium Seating, Public Assembly - Libraries, Public Assembly - Museums, Retail - General, Retail - Mall Common Areas, Retail - Supermarket, Residential - Common Corridors, Residential - Living Area Default: "Commercial - Office Buliding - Office Space" |
occupant_density_methodSelect standard density or activate custom_occupant_density. Units: source enum. Omitted input retains publisher's source default "ASHRAE 62.1-2022 Occupant Density". | Type: string Constraints: one of: ASHRAE 62.1-2022 Occupant Density, User-Defined Occupant Density Default: "ASHRAE 62.1-2022 Occupant Density" |
custom_occupant_densityActive only in User-Defined Occupant Density mode; must supply nonnegative numeric value when activating. Omitted baseline is formula placeholder "-" and is not a numeric assumption. Units: persons/m². Omitted input retains publisher's source default "-". | Type: number Constraints: min: 0 |
flow_rate_methodSelect standard rates or activate both custom flow-rate ports. Units: source enum. Omitted input retains publisher's source default "ASHRAE 62.1-2022 Flow Rates". | Type: string Constraints: one of: ASHRAE 62.1-2022 Flow Rates, User-Defined Flow Rates Default: "ASHRAE 62.1-2022 Flow Rates" |
custom_flow_per_areaActive only in User-Defined Flow Rates mode; supply alongside custom_flow_per_person. Omitted baseline is formula placeholder "-". Units: L/s/m². Omitted input retains publisher's source default "-". | Type: number Constraints: min: 0 |
custom_flow_per_personActive only in User-Defined Flow Rates mode; supply alongside custom_flow_per_area. Omitted baseline is formula placeholder "-". Units: L/s/person. Omitted input retains publisher's source default "-". | Type: number Constraints: min: 0 |
doas_velocity_m_per_sDedicated outdoor air shaft velocity Units: m/s. Omitted input retains publisher's source default 8. | Type: number Constraints: min: 0.01 Default: 8 |
doas_safety_fractionDOAS shaft oversizing margin (0.15 means 15%) Units: decimal fraction. Omitted input retains publisher's source default 0.15. | Type: number Constraints: min: 0 Default: 0.15 |
peak_heating_kwPeak sensible heating load Units: kW. Omitted input retains publisher's source default 170. | Type: number Constraints: min: 0 Default: 170 |
peak_cooling_kwPeak sensible cooling load Units: kW. Omitted input retains publisher's source default 240. | Type: number Constraints: min: 0 Default: 240 |
cooling_setpoint_cCooling setpoint must exceed supply_air_temperature_c Units: °C. Omitted input retains publisher's source default 24. | Type: number Default: 24 |
heating_setpoint_cHeating setpoint must exceed supply_air_temperature_c for the source calculation Units: °C. Omitted input retains publisher's source default 18. | Type: number Default: 18 |
all_air_velocity_m_per_sAll-air supply shaft velocity Units: m/s. Omitted input retains publisher's source default 8. | Type: number Constraints: min: 0.01 Default: 8 |
all_air_safety_fractionAll-air shaft oversizing margin (0.15 means 15%) Units: decimal fraction. Omitted input retains publisher's source default 0.15. | Type: number Constraints: min: 0 Default: 0.15 |
Outputs (5)
| Port / description | Type / constraints / default |
|---|---|
people_countOccupant count Units: persons. Positive unless stated otherwise. | Type: number |
outdoor_flow_l_per_sTotal ventilation outdoor airflow Units: L/s. Positive unless stated otherwise. | Type: number |
doas_total_shaft_m2Combined DOAS supply and exhaust shaft area Units: m². Positive unless stated otherwise. | Type: number |
all_air_total_shaft_m2Combined all-air supply and return shaft area Units: m². Positive unless stated otherwise. | Type: number |
shaft_comparisonSource textual comparison of DOAS and all-air shafts Units: text. Positive unless stated otherwise. | Type: string |
Questions this workbook answers
- MIT BuildVac ventilation requirements calculator
- ASHRAE 62.1 outdoor airflow shaft area
- DOAS versus all-air shaft sizing
Questions and answers
Which standard and units are used?
The source labels ASHRAE 62.1-2022. Area is m², outdoor rates L/s, loads kW, temperatures °C and safety margins decimal fractions.
How do custom occupancy and flow rates work?
Select User-Defined Occupant Density and supply persons/m². Select User-Defined Flow Rates and supply both L/s/m² and L/s/person.
For agents
Connect an MCP client to the catalog endpoint:
https://catalog.formualizer.com/v1/mcpSlug: mit-buildvac-ventilation · Edition: v1.0
- search_workbooks
- Optional arguments: query (string), theme (string), tag (string).
- inspect_workbook
- Required: slug (string). Optional: edition (string), flow (string).
- evaluate_workbook
- Required: slug (string), inputs (object). Optional: edition (string), flow (string), cellOverrides (object), selectCells (array of strings), trace (boolean).
{
"name": "evaluate_workbook",
"arguments": {
"slug": "mit-buildvac-ventilation",
"edition": "v1.0",
"flow": "quick_ventilation_shafts",
"inputs": {
"program_area_m2": 10000
}
}
}cellOverrides sets individual cells. selectCells reads at most 256 cells per request. trace requests formula lineage.
Flows
quick_ventilation_shafts
Quick ventilation and shaft comparison
Compare DOAS and all-air shafts with coupled density/rate method switches. Supply all custom numeric ports when activating their methods. Baseline supply temperature 12.8°C and air properties remain pinned.
15 input ports · 5 output ports. Full membership in the port contract.
full_ventilation_assessment
Full ventilation and all-air assessment
All source decision inputs including air properties and supply temperature, plus supply/return/exhaust diagnostics. Fixed return ratio 80%; source lookup table is pinned.
18 input ports · 12 output ports. Full membership in the port contract.
REST example
Bundle scenario: quick_ventilation_shafts_larger_office · Flow: quick_ventilation_shafts
curl 'https://catalog.formualizer.com/v1/models/mit-buildvac-ventilation/v1.0/evaluate?flow=quick_ventilation_shafts' \
-H 'Content-Type: application/json' \
--data '{"inputs":{"program_area_m2":10000}}'Expected response
Expected values from the bundle, subject to the check level above.
{
"outputs": {
"people_count": 500,
"outdoor_flow_l_per_s": 4250,
"doas_total_shaft_m2": 1.2218749999999998,
"all_air_total_shaft_m2": 6.995576139985888,
"shaft_comparison": "Shafts for the all-air system are larger than shafts for the dedicated outdoor air system"
}
}Looking for another spreadsheet? Request a workbook.