MIT BuildVac Ventilation Requirements

MIT Sustainable Design Lab

Estimate outdoor, heating and cooling airflow. Size supply and exhaust shafts for dedicated outdoor air and supply and return shafts for all-air systems.

Inputs
18
Outputs
12
File size
35 KB
Verification
Independent scenario check

Try it

Try it loads a copy of this file from formualizer.com.

CALCULATIONB5:D44

Saved workbook valuesInputOutput

RowBCD
5Program Area (m2)5000
6ProgramCommercial - Office Buliding - Office Space
7Occupant Density MethodASHRAE 62.1-2022 Occupant Density
9Total People Count250
12Flow Rate MethodASHRAE 62.1-2022 Flow Rates
19Air Velocity (m/s)8
29Peak Heating Load (kW)170
30Peak Cooling Load (kW)240

What was checked

Changed-input scenarios match an independent calculation.

Scope and limitations

Catalog calculations, not certification.

Try it uses Formualizer’s exact-match program lookups for the listed building types.

MIT BuildVac Ventilation Requirements with version-pinned publisher workbook calculations, scenario inputs and formula-level audit traces.

  • Edition v1.0 is a catalog pin, not a separately established publisher release number.
  • Heating uses the same cold supply temperature as cooling exactly as authored; this conceptual comparison is not full HVAC design.
  • Runtime approximate VLOOKUP fails exact source default on unsorted Lists!A1:D18. Exact-match adaptation is bounded to documented program enum; source bytes are unchanged.

What it computes

Ports for the compact flow: quick_ventilation_shafts. The full port contract includes all 30 ports.

Inputs (15)
Port / descriptionType / constraints / default
program_area_m2

Nonnegative floor program area. Units: m². Omitted input retains publisher's source default 5000.

Type: number

Constraints: min: 0

Default: 5000

program

Exact source program label; preserve source spelling Buliding and double spaces. Three lookups use documented exact-match preparation for these labels. Units: source enum. Omitted input retains publisher's source default "Commercial - Office Buliding - Office Space".

Type: string

Constraints: one of: Commercial - Office Buliding - Lobbies and Corridors, Commercial - Office Buliding - Office Space, Education - Assembly, Education - Classrooms (5-8), Education - Classrooms (9+), Education - Lecture Classroom, Education - Lecture Hall, Education - Libraries, Education - University Laboratory, Public Assembly - Auditorium Seating, Public Assembly - Libraries, Public Assembly - Museums, Retail - General, Retail - Mall Common Areas, Retail - Supermarket, Residential - Common Corridors, Residential - Living Area

Default: "Commercial - Office Buliding - Office Space"

occupant_density_method

Select standard density or activate custom_occupant_density. Units: source enum. Omitted input retains publisher's source default "ASHRAE 62.1-2022 Occupant Density".

Type: string

Constraints: one of: ASHRAE 62.1-2022 Occupant Density, User-Defined Occupant Density

Default: "ASHRAE 62.1-2022 Occupant Density"

custom_occupant_density

Active only in User-Defined Occupant Density mode; must supply nonnegative numeric value when activating. Omitted baseline is formula placeholder "-" and is not a numeric assumption. Units: persons/m². Omitted input retains publisher's source default "-".

Type: number

Constraints: min: 0

flow_rate_method

Select standard rates or activate both custom flow-rate ports. Units: source enum. Omitted input retains publisher's source default "ASHRAE 62.1-2022 Flow Rates".

Type: string

Constraints: one of: ASHRAE 62.1-2022 Flow Rates, User-Defined Flow Rates

Default: "ASHRAE 62.1-2022 Flow Rates"

custom_flow_per_area

Active only in User-Defined Flow Rates mode; supply alongside custom_flow_per_person. Omitted baseline is formula placeholder "-". Units: L/s/m². Omitted input retains publisher's source default "-".

Type: number

Constraints: min: 0

custom_flow_per_person

Active only in User-Defined Flow Rates mode; supply alongside custom_flow_per_area. Omitted baseline is formula placeholder "-". Units: L/s/person. Omitted input retains publisher's source default "-".

Type: number

Constraints: min: 0

doas_velocity_m_per_s

Dedicated outdoor air shaft velocity Units: m/s. Omitted input retains publisher's source default 8.

Type: number

Constraints: min: 0.01

Default: 8

doas_safety_fraction

DOAS shaft oversizing margin (0.15 means 15%) Units: decimal fraction. Omitted input retains publisher's source default 0.15.

Type: number

Constraints: min: 0

Default: 0.15

peak_heating_kw

Peak sensible heating load Units: kW. Omitted input retains publisher's source default 170.

Type: number

Constraints: min: 0

Default: 170

peak_cooling_kw

Peak sensible cooling load Units: kW. Omitted input retains publisher's source default 240.

Type: number

Constraints: min: 0

Default: 240

cooling_setpoint_c

Cooling setpoint must exceed supply_air_temperature_c Units: °C. Omitted input retains publisher's source default 24.

Type: number

Default: 24

heating_setpoint_c

Heating setpoint must exceed supply_air_temperature_c for the source calculation Units: °C. Omitted input retains publisher's source default 18.

Type: number

Default: 18

all_air_velocity_m_per_s

All-air supply shaft velocity Units: m/s. Omitted input retains publisher's source default 8.

Type: number

Constraints: min: 0.01

Default: 8

all_air_safety_fraction

All-air shaft oversizing margin (0.15 means 15%) Units: decimal fraction. Omitted input retains publisher's source default 0.15.

Type: number

Constraints: min: 0

Default: 0.15

Outputs (5)
Port / descriptionType / constraints / default
people_count

Occupant count Units: persons. Positive unless stated otherwise.

Type: number

outdoor_flow_l_per_s

Total ventilation outdoor airflow Units: L/s. Positive unless stated otherwise.

Type: number

doas_total_shaft_m2

Combined DOAS supply and exhaust shaft area Units: m². Positive unless stated otherwise.

Type: number

all_air_total_shaft_m2

Combined all-air supply and return shaft area Units: m². Positive unless stated otherwise.

Type: number

shaft_comparison

Source textual comparison of DOAS and all-air shafts Units: text. Positive unless stated otherwise.

Type: string

Questions this workbook answers

  • MIT BuildVac ventilation requirements calculator
  • ASHRAE 62.1 outdoor airflow shaft area
  • DOAS versus all-air shaft sizing

Questions and answers

Which standard and units are used?

The source labels ASHRAE 62.1-2022. Area is m², outdoor rates L/s, loads kW, temperatures °C and safety margins decimal fractions.

How do custom occupancy and flow rates work?

Select User-Defined Occupant Density and supply persons/m². Select User-Defined Flow Rates and supply both L/s/m² and L/s/person.

For agents

Connect an MCP client to the catalog endpoint:

https://catalog.formualizer.com/v1/mcp

Slug: mit-buildvac-ventilation · Edition: v1.0

search_workbooks
Optional arguments: query (string), theme (string), tag (string).
inspect_workbook
Required: slug (string). Optional: edition (string), flow (string).
evaluate_workbook
Required: slug (string), inputs (object). Optional: edition (string), flow (string), cellOverrides (object), selectCells (array of strings), trace (boolean).
{
  "name": "evaluate_workbook",
  "arguments": {
    "slug": "mit-buildvac-ventilation",
    "edition": "v1.0",
    "flow": "quick_ventilation_shafts",
    "inputs": {
      "program_area_m2": 10000
    }
  }
}

cellOverrides sets individual cells. selectCells reads at most 256 cells per request. trace requests formula lineage.

Flows

quick_ventilation_shafts

Quick ventilation and shaft comparison

Compare DOAS and all-air shafts with coupled density/rate method switches. Supply all custom numeric ports when activating their methods. Baseline supply temperature 12.8°C and air properties remain pinned.

15 input ports · 5 output ports. Full membership in the port contract.

full_ventilation_assessment

Full ventilation and all-air assessment

All source decision inputs including air properties and supply temperature, plus supply/return/exhaust diagnostics. Fixed return ratio 80%; source lookup table is pinned.

18 input ports · 12 output ports. Full membership in the port contract.

REST example

Bundle scenario: quick_ventilation_shafts_larger_office · Flow: quick_ventilation_shafts

curl 'https://catalog.formualizer.com/v1/models/mit-buildvac-ventilation/v1.0/evaluate?flow=quick_ventilation_shafts' \
  -H 'Content-Type: application/json' \
  --data '{"inputs":{"program_area_m2":10000}}'

Expected response

Expected values from the bundle, subject to the check level above.

{
  "outputs": {
    "people_count": 500,
    "outdoor_flow_l_per_s": 4250,
    "doas_total_shaft_m2": 1.2218749999999998,
    "all_air_total_shaft_m2": 6.995576139985888,
    "shaft_comparison": "Shafts for the all-air system are larger than shafts for the dedicated outdoor air system"
  }
}